Commercial Heat Pump

The world’s top heat pump compressor COPELAND, PANASONIC, HITACHI
Adopt international famous brand, and enhanced vapor injection technology, reaching the highest level of efficiency within the air source industry. The strong kernel and high stanility ensure the long life of the unit and save more operating cost.
Coil heat exchanger TITANIUM / COPPER
Coil heat exchanger, pushes water temperature up to 80 celcius degree, and thus it can be widely used in both house and water heating, completely replacing the traditional heating equipment. High double pipe heat exchanger is good more than 2 times compared with box exchanger - consists of many red copper pipe or Titanium spring coil and put into metal box coated with high pressure anti-corrosion materials.
Double way condenser - high efficiency
Area of condenser raised to maimum - exchanger fin density increased two times more than other - to reach COP range from 3.8 to 6.5. Compared with plain films and louver fins, the hydrophilic concave-convex fins possess higher thermal efficiency. The corrugated structure makes condensed water turn into channels easily and accelerates the water discharge. Defrosting is effective. The evaporator gets rid of freezing.
Fan and Motor
The high quality of the fan and motor system ensures a quite and stable working condition and sufficient air for heat exchange.
Auto Defrosting System
4-way valve is adopted in automatic defrosting system to reach fast and high efficiency defrosting.
Wiring Connection / Slot type mother board
Clear and inner wiring connection provides convenience of installation and further maintenance.
Intelligent LED Controller
Advanced all-in-one technology to realize multi functional usage.
Technical specification
No. | Model No. | MGS-3HP | MGS-5HP | MGS-6HP | MGS-10HP | MGS-15HP | MGS-18HP | MGS-20HP |
I | HEATING CAPACITY & POWER INPUT (Outdoor air temperature at 20 Celcius degree; Outlet water temperature at 55 Celcius degree) | |||||||
1 | Heating capacity (KW) | 10.5 | 19 | 22 | 38 | 42 | 52 | 72 |
2 | Input power (KW) | 2.55 | 4.6 | 5.3 | 9.22 | 10.22 | 12.44 | 17.18 |
3 | Productivity (L/h) | 226 | 408 | 473 | 817 | 903 | 1118 | 1548 |
4 | Coefficient of performance (COP) | 4.12 | 4.13 | 4.15 | 4.12 | 4.11 | 4.18 | 4.19 |
II | GENERAL INFORMATION | |||||||
1 | Scroll compressor x pcs | Copeland x 1 pcs | Copeland x 1 pcs | Copeland x 1 pcs | Copeland x 2 pcs | Copeland x 2 pcs | Copeland x 2 pcs | Copeland x 4 pcs |
2 | No. of Axial fan | 1 pcs | 1 pcs | 1 pcs | 2 pcs | 2 pcs | 2 pcs | 2 pcs |
3 | Refrigerant | R417A | ||||||
4 | Rated outlet water temperature (℃) | 55℃ | ||||||
5 | Max outlet water temperature (℃) | 60℃ | ||||||
6 | Working temperature (℃) | 0℃ to 45℃ | ||||||
7 | Evaporator | Aluminium fins & copper tube - Option: Copper fins & copper tube | ||||||
8 | Heat exchanger – Condenser | Copper tube in tube or in shell - Option: Double wall heat exchanger | ||||||
9 | Case materials | Glavanzied steel with powder paint coating - Option : Stainless steel SUS304 - Good for sea area | ||||||
10 | Electric system | Schneider / Siemens | ||||||
11 | Controller | Auto intelligent controller - Option: RS485, wifi, connect to BMS | ||||||
12 | Protection | Low Pressure Switch - 0.05/0.15MPa ; High Pressure Switch : 2.6/3.2Mpa - Over current protection, over heat, phase loss, phase reversal, flow switch | ||||||
13 | Water grade | IPX4 | ||||||
14 | Noise (dB) | ≤52 | ≤55 | ≤55 | ≤66 | ≤66 | ≤68 | ≤70 |
III | ELECTRIC SPECIFICATION | |||||||
1 | Input power | 380V/50HZ | ||||||
2 | Rate current (A) | 5.0 | 9.0 | 10.4 | 18.2 | 20.1 | 24.6 | 33.7 |
3 | Max current (A) | 7.5 | 13.5 | 15.6 | 27.3 | 30.2 | 36.9 | 50.6 |
4 | Recommended MCCB (A) | 15 | 20 | 25 | 40 | 50 | 63 | 80 |
5 | Recommended cabble | 3*4mm2 +2*2.5mm2 | 3*6mm2 +2*2.5mm2 | 3*6mm2 +2*2.5mm2 | 3*10mm2 +2*4mm2 | 3*10mm2 +2*4mm2 | 3*10mm2 +2*4mm2 | 3*16mm2 +2*6mm2 |
6 | Anti-electric shock rate | I | I | I | I | I | I | I |
IV | WATER & AIR SPECIFICATION | |||||||
1 | Water source circulating flow (m3/H) | 2.50 | 4.50 | 5.00 | 9.00 | 10.00 | 12.00 | 15.00 |
2 | Water pressure drop (KPa) | ≤40 | ≤65 | ≤68 | ≤68 | ≤70 | ≤78 | ≤80 |
3 | Inlet water pipe size (mm) | DN25 | DN25 | DN25 | DN40 | DN40 | DN40 | DN50 |
4 | Nominal air flow (m3/H) | 3,950 | 5,000 | 6,500 | 12,000 | 15,000 | 17,000 | 20,000 |
5 | Fan direction | Top fan | ||||||
V | DIMENSION & WEIGHT | |||||||
1 | Case dimension (LxWxH) (mm) | 710*710*1070 | 800*800*1070 | 800*800*1070 | 1500*800*1070 | 1500*800*1070 | 1500*800*1070 | 1850*1000*1950 |
2 | Net weight (kg) | 90 | 125 | 135 | 280 | 372 | 395 | 482 |
No. | Model No. | MGS-25HP | MGS-30HP | MGS-35HP | MGS-40HP | MGS-44HP | MGS-52HP |
I | HEATING CAPACITY & POWER INPUT (Outdoor air temperature at 20 Celcius degree; Outlet water temperature at 55 Celcius degree) | ||||||
1 | Heating capacity (KW) | 92 | 106 | 125 | 138 | 158 | 200 |
2 | Input power (KW) | 22.12 | 25.54 | 30.34 | 33.41 | 38.07 | 48.19 |
3 | Productivity (L/h) | 1978 | 2278 | 2687 | 2966 | 3396 | 4299 |
4 | Coefficient of performance (COP) | 4.16 | 4.15 | 4.12 | 4.13 | 4.15 | 4.15 |
II | GENERAL INFORMATION | ||||||
1 | Scroll compressor x pcs | Copeland x 4 pcs | Copeland x 4 pcs | Copeland x 3 pcs | Copeland x 3 pcs | Copeland x 4 pcs | Copeland x 4 pcs |
2 | No. of Axial fan | 2 pcs | 2 pcs | 2 pcs | 3 pcs | 4 pcs | 4 pcs |
3 | Refrigerant | R417A | |||||
4 | Rated outlet water temperature (℃) | 55℃ | |||||
5 | Max outlet water temperature (℃) | 60℃ | |||||
6 | Working temperature (℃) | 0℃ to 45℃ | |||||
7 | Evaporator | Aluminium fins & copper tube - Option: Copper fins & copper tube | |||||
8 | Heat exchanger – Condenser | Copper tube in tube or in shell - Option: Double wall heat exchanger | |||||
9 | Case materials | Glavanzied steel with powder paint coating - Option : Stainless steel SUS304 - Good for sea area | |||||
10 | Electric system | Schneider / Siemens | |||||
11 | Controller | Auto intelligent controller - Option: RS485, wifi, connect to BMS | |||||
12 | Protection | Low Pressure Switch - 0.05/0.15MPa ; High Pressure Switch : 2.6/3.2Mpa - Over current protection, over heat, phase loss, phase reversal, flow switch | |||||
13 | Water grade | IPX4 | |||||
14 | Noise (dB) | ≤72 | ≤75 | ≤75 | ≤75 | ≤80 | ≤80 |
III | ELECTRIC SPECIFICATION | ||||||
1 | Input power | 380V/50HZ | |||||
2 | Rate current (A) | 43.6 | 50.7 | 60.2 | 66.3 | 75.6 | 95.7 |
3 | Max current (A) | 65.4 | 76.1 | 90.3 | 99.5 | 113.4 | 143.6 |
4 | Recommended MCCB (A) | 100 | 120 | 125 | 150 | 200 | 200 |
5 | Recommended cabble | 3*16mm2 +2*6mm2 | 3*16mm2 +2*10mm2 | 3*16mm2 +2*10mm2 | 3*16mm2 +2*10mm2 | 3*25mm2 +2*10mm2 | 3*25mm2 +2*10mm2 |
6 | Anti-electric shock rate | I | I | I | I | I | I |
IV | WATER & AIR SPECIFICATION | ||||||
1 | Water source circulating flow (m3/H) | 20.00 | 23.00 | 27.00 | 30.00 | 34.00 | 43.00 |
2 | Water pressure drop (KPa) | ≤85 | ≤85 | ≤85 | ≤88 | ≤88 | ≤88 |
3 | Inlet water pipe size (mm) | DN65 | DN80 | DN80 | DN80 | DN80 | DN80 |
4 | Nominal air flow (m3/H) | 24,000 | 34,000 | 36,000 | 45,000 | 48,000 | 60,000 |
5 | Fan direction | Top fan | |||||
V | DIMENSION & WEIGHT | ||||||
1 | Case dimension (LxWxH) (mm) | 1750*1120*1000 | 2200*1100*2000 | 2200*1100*2000 | 3200*1300*2000 | 2005*1825*1900 | 2130*2140*1920 |
2 | Net weight (kg) | 582 | 700 | 720 | 850 | 1050 | 1200 |